| GZS1 type of metal-clad draw-out switchgear |
|
| 一、Brief instruction |
The GZS1 Indoor metal-clad draw-out
switchboard (Herein after called as
switchboard) made in Anhui Xinlong electrical
company is a assembled electrical power
distributing equipment for AC. 3.6 ~12
KV, 3 phases, 50Hz, signal or double
bus-bar system, mainly used in power
distributing system of Elec. Power plants,
power transmitting work-net, industries
and secondary substations as receiving
and distributing equipment or as a controlling
or protecting or supervising equipment
of starting H. voltage motors, and so
on. The switchboard meets with IEC298,
GB3906 standards, having had many features
that preventing circuit breaker truck
from being pulled out with load, preventing
the circuit breaker from being mal-operated
by close or open, preventing persons
from entering into live chambers and
preventing earthing switch from being
closed when main breaker is closed.
The switchboard is equipped with VS1
vacuum breaker or EV12 vacuum circuit
breaker of Schneider Co. or VD4 vacuum
breaker of ABB Co. as Main breaker or.
The switchboard is reliable and high
electrical performance electrical distributing
equipment. |
|
| 二、Explanation of the model |
 |
| 三、Application conditions |
--- Ambient Temperature: Max. Temp.: +40℃, Min. Temp. -10℃
--- Relative humidity: Average
relative humidity/day:
≤95%;
Average relative humidity/month: ≤90%.
--- Altitude:
Altitude is not higher than 1000 M.
(If altitude is higher
than 1000M. DL/T593-1996 shall be applied).
--- Vibration
degree is not over 8 degree.
--- The
switchgear is suitable for use in a place
where no fire, explosive material, serious
sewage and chemical corrosion.
Note: If conditions of
applied environment are beyond required
conditions, it is necessary to have a discussion
with the manufacturer.
|
| 四、Main
technical parameters of the switchboard |
| Description |
Unit |
Main technical parameter |
| Rated voltage |
kV |
3.6,7.2,12 |
| Max. Operating voltage |
kV |
3.6,7.2,12 |
| Rated insulated level |
Rated power frequency withstand voltage
(1 Min) |
kV |
42 |
| Rated lightning impulse withstand voltage
(Peak) |
kV |
75 |
| Rated frequency |
Hz |
50 |
| Rated current of main busbar |
A |
630,1250,1600,2000,2500,3150 |
| Rated current of branch busbar |
A |
630,1250,1600,2000,2500,3150 |
| Rated thermal stability current / 3s |
kA |
25,31.5,40,50 |
| Rated dynamical stability current (Peak)* |
kA |
63,80,100,125 |
| Enclosure protective degree |
IP4X; IP2X when door
of breaker chamber is open. |
|
|
|